DIMM – Dual Input Monitor Module

Description
The Hochiki Dual Monitor Module (DIMM) is designed for use on the FireNET analog addressable system. It provides two independent contact monitoring circuits while only utilizing one address on the SLC loop. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contact fire alarm and supervisory devices. The interrupt driven Digital Communication Protocol (DCP) combines maximum communication reliability and fast response to emergency conditions. The module has a single bi-colored LED to indicate device status. It fits into a standard 4″ square or double gang electrical back box.

Standard Features

  • Fast, reliable contact monitoring utilizing the Hochiki DCP (Digital Communications Protocol)
  • 127 devices can be used per DCP loop
  • Bi-colored indicating LED provides module status
  • Dual input contact monitor
  • Can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts
  • Operates on Class A or Class B SLC loop
  • Accepts up to 14 AWG wire
  • Mounts to 4″ square gang box